Schneider Electric XPSMF2DO801 Network Hardware User Manual


 
Equipment Description
56
33003405 07/2007
Operating Conditions
Overview The XPSMF2DO801 safety remote output module has been developed in
compliance with the requirements of the following standards for EMC, climate and
environment:
To use the XPSMF2DO801 safety remote output module, the following conditions
must be fulfilled:
Climatic
Conditions
The most important tests and limit values for climatic conditions are listed in the
following table:
IEC 61131-2 Programmable Controllers, Part 2, Equipment Requirements and
Tests
IEC 61000-6-2 EMC Generic Standards, Part 6-2
IEC 61000-6-4 EMC General Emission Standard, Industrial Environment
Protection Class Protection class II according to IEC/EN 61131-2
Pollution Pollution degree II
Altitude < 2000 m / 6561.7 ft
Enclosure Standard: IP 20 If requested by the relevant application standards
(e.g., EN 60204, EN 954-1), the device must be installed in a required
enclosure (e.g., IP 54).
EN 61131-2 Climatic Tests
Operating temperature: 0°C to 60°C / 32°F to 140°F
(Test limits -10°C to +70°C / 14°F to 158°F)
Storage temperature: -40°C to 85°C / -40°F to 185°F (with battery
only -30°C / -22°F)
6.3.4.2 Dry heat and cold withstand test: 70°C / -25°C (158°F / -13°F, 96 h,
EUT power supply disconnected
6.3.4.3 Change of temperature, withstand and immunity test: -25°C / 70°C
(-13°F / 158°F) and 0°C / 55°C (32°F / 131°F), EUT power supply
disconnected
6.3.4.4 Cyclic damp heat withstand test: 25°C / 55°C (77°F / 131°F), 95%
relative humidity, EUT power supply disconnected