Schneider Electric XPSMF2DO801 Network Hardware User Manual


 
Application and Function
33003405 07/2007 33
Maintenance The XPSMF2DO801 safety remote output module is designed for industrial
applications. All the components have a very high availability and are compliant with
the requirements of IEC 61508 for PFD and PFH in accordance with SIL 3.
Repair of Remote
Output Modules
You may not repair the XPSMF2DO801 safety remote output device. Defective
devices must be returned to Schneider Electric for repair.
The validity of the safety certificate will expire if unauthorized repairs have been
made on the device. The manufacturer will bear no responsibility for unauthorized
repairs. Unauthorized repairs will also cancel all warranties for the device.
Note: For safety-related use, the modules have to be subjected to an offline proof
test in intervals of 3 years. For Offline Proof Test, see Offline Proof-Test, p. 34.
OFFLINE PROOF TEST
Offline Proof Test according to IEC 61508-4 must be conducted to verify proper
operation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING