2. Installation
INSTALLATION CONSIDERATIONS
ALERT
!
ALERT! This product must be installed and maintained
only by qualified personnel. Verify all connections
meet requirements specified in local electric codes or
operating company guidelines before supplying power.
Protect this equipment with a fuse or breaker sufficient
to interrupt power levels specified in Section 1 of this
manual.
— Tools and Equipment
•
7
/16 in. (or 12 mm) socket for
1
/4-in. bolts and KEPS nuts
•
9
/16 (or 14 mm) socket for
3
/8-in. bolts and nuts
• #2 Phillips screwdriver (screwdriver for cross-recessed
screws)
• standard electrical cabling tools (cable lacing, crimping
and stripping tools, cable cutters, etc.)
— Technical Support
By e-mail: getinfo@telect.com
By phone: 888-821-4856 or 509-921-6161
INSPECTION
Compare the contents of the shipping container with the packing
list. Call Telect if anything is missing.
NOTE
Telect is not liable for shipping damage.
If the shipping container is damaged, keep it for the carrier’s
inspection. Notify the carrier and call Telect’s Customer Ser-
vice Department:
1-800-551-4567 or 1-509-926-6000
Keep the container until you have checked equipment opera-
tion. If you experience any kind of problem, call Telect’s Cus-
tomer Service Department. Use the original, undamaged con-
tainer if you are instructed to return the BDFB / BDCBB to
Telect.
BAY LAYOUT
In a standard bay, each BDFB / BDCBB requires 10 EIA
rack positions (10 RU). Up to four BDFB / BDCBB panels
can populate a bay having either 19-in. or 23-in. racks (ei-
ther EIA or WECO spacing).