Telect 007-0001-2600 Network Router User Manual


 
Telect, Inc. • USA +1.509.926.6000 • Mexico +1.52.33.3836.3700
Poland +1.48.713.239.100 • UK +1.44.1489.889500 • www.telect.com
Copyright © 2002 Telect, Inc., All Rights Reserved
Page 2-5
Follow the prescribed order in this subsection to install and test all cabling and alarm features:
A.Install Ground Cabling
B.Install Input Cabling
C.Install Intrabay & Interbay Cabling
D. Install Alarm Cabling
E.Test Inputs and Alarms Without Circuit Breakers
F.Install Output Cabling
— A. Install Ground Cabling
DANGER
!
DANGER! DANGER! Failure to properly ground this equipment can create hazardous conditions to installa-
tion personnel and to the equipment.
GEFAHR! Bei unsachgemäßer Erdung besteht Gefahr für das Installationspersonal und das Gerät!
¡PELIGRO! La conexión incorrecta a tierra puede ser peligrosa tanto para los instaladores como para el equi-
po.
DANGER ! Si vous ne reliez pas correctement cet équipement à la terre, son utilisation présente des dangers
pour la personne qui l'installe ainsi que pour l'équipement.
A ground terminal is located near each of the panel’s mounting flanges. You need only connect to one of the grounds, as shown in
the following illustration.
1. Use a UL-approved crimping tool to attach a UL-approved, 2-hole compression lug onto a ground wire.
Size of ground depends on input interruption device.
1
2. Lightly coat anti-oxidant electrical joint compound on lug, grounding terminal, and surrounding contacting surface. Then, con-
nect lug to terminal using
1
/4-in. KEPS nuts and washers from studs.
1. Refer to NEC Article 250-122 or IEEE grounding guidelines. Also, check operating company guidelines.