8. Repeat Steps 5 through 7 for all other breakers and corresponding loads.
After the last breaker is turned on, the FUSE ALM lamp must go off.
9. Use an ohmmeter at alarm monitor to verify powered-up circuit breaker (fuse) alarm condition.
With all circuit breakers ON and powered up, expect either continuity (0 Ω) between C and NC poles or an open circuit (∞ Ω) be-
tween and C and NO.