7. Network Characteristics Configuration
The MDB-100 interface board uses an 8-position DIP switch (labeled SW1) to
configure the Modbus network communication characteristics. The switch settings
are only read during initialization, so if a change is made to any of the switches on
SW1, the MDB-100 must be reset in order to enable the new settings. The various
configuration settings of switch SW1 are as follows:
Communication Method:
SW1 #
1
Function
OFF Modbus RTU (factory default)
ON Modbus ASCII
Baud Rate:
SW1 #
4 3 2
Function
OFF OFF OFF 300 baud
OFF OFF ON 600 baud
OFF ON OFF 1200 baud
OFF ON ON 2400 baud
ON OFF OFF 4800 baud
ON OFF ON 9600 baud (factory default)
ON ON OFF 19.2 kbaud
ON ON ON 38.4 kbaud
Parity:
SW1 #
6 5
Function
OFF OFF even parity (factory default)
OFF ON odd parity
ON OFF no parity (2 stop bits)
ON ON no parity (1 stop bit) - applies only to RTU mode
Protocol:
SW1 #
7
Function
OFF Modicon Modbus (factory default)
ON DO NOT SELECT (reserved for future expansion)
Station Number Origin:
(refer to section 8)
SW1 #
8
Function
OFF Drive A’s inverter number parameter (factory default)
ON Switch SW2 address setting