Toshiba MDB-100 Network Card User Manual


 
2
Usage Precautions
Please use the MDB-100 only when the ambient temperature of the environment into
which the MDB-100 is installed is within the following specified temperature limits:
Operation
: -10
+40
°
C (+14
+104
°
F)
Storage
: -25
+65
°
C (-13
+149
°
F)
Avoid installation locations that may be subjected to large shocks or vibrations.
Avoid installation locations that may be subjected to rapid changes in temperature or
humidity.
Operating Environment
Do not touch charged parts of the drive such as the terminal block while the drive’s
CHARGE lamp is lit. A charge will still be present in the drive’s internal electrolytic
capacitors, and therefore touching these areas may result in an electrical shock.
Always turn all drive input power supplies OFF, and wait at least 5 minutes after the
CHARGE lamp has gone out before connecting communication cables or motor wiring.
Route all communication cables separate from the inverter input/output power wiring.
To avoid the possibility of electric shock due to leakage currents, always ground the
inverter unit’s E/GND terminal and the motor. To avoid misoperation, do not connect
the MDB-100’s SHIELD terminal to either of the above-mentioned grounds or any other
power ground.
When making connections between the MDB-100 and S7 drives, do not use cables
that exceed 5 meters in length.
For further drive-specific precaution, safety and installation information, please refer to
the appropriate Toshiba documentation supplied with your S7 drive.
Installation
Wiring
The drive’s EEPROM has a life span of 10,000 write cycles. Do not write to the same
holding register (other than registers 7A00
7A02 and FA00
FA02 or write-only coils)
more than 10,000 times.
The MDB-100’s EEPROM has a life span of 100,000 write cycles. Do not write to the
same MDB-100 configuration register more than 100,000 times.
Do not touch or insert a rod or any other item into the MDB-100’s case while power is
applied, as this may lead to electrical shock or device damage.
Commission the disposal of the MDB-100 to a specialist.
Do not assign the same network address to more than one MDB-100 station in the
same network. For a detailed explanation of station addressing, refer to section 8.
When the MDB-100 is configured to receive its Modbus RTU / ASCII station address
from the drive on Channel A, be sure to reset the MDB-100 if the inverter number
parameter on the drive on Channel A is changed. Refer to section 8 for more
information.
Because the MDB-100 derives its control power from the drive connected to Channel
A, removing power from that drive will also cause the MDB-100 to lose power, even if
power is still applied to the drive connected to channel B.
When only 1 drive is connected to the MDB-100, it must be connected to Channel A.
Other Precautions