Xantrex Technology XW4548-120/240-60 Power Supply User Manual


 
Specifications
A–2 975-0239-01-01
Electrical Specifications
Table A-1
XW Power System Electrical Specifications
Model XW6048-120/240-60 XW4548-120/240-60 XW4024-120/240-60
Continuous Output Power 6,000 W 4,500 W 4,000 W
Surge Rating (10 seconds) 12,000 W 9,000 W 8,000 W
Surge Current L-n: 105 A
rms
(7 sec)
L-L: 52.5 A
rms
(7 sec)
L-n: 75 A
rms
(20 sec)
L-L: 40 A
rms
(20 sec)
L-n: 70 A
rms
(7 sec)
L-L: 35 A
rms
(7 sec)
Waveform True Sine Wave
Idle Consumption—invert mode, no load 28 W 26 W 24 W
Idle Consumption—search mode < 8 W
AC Output Voltage L-n: 120 Vac ±3%
L-L: 240 Vac ±3%
AC Input voltage range (Bypass/Charge
Mode)
L-n: 80–150 Vac (120 V nominal)
L-L: 160–270 Vac (240 V nominal)
AC Input Current (maximum 75%
imbalance between L1-n, L2-n)
L-n: 41.2 A
L-L: 27.5 A
L-n: 30.9 A
L-L: 20.6 A
L-n: 27.5 A
L-L: 18.3 A
AC Input Breaker 60 A double-pole
AC Input Frequency Range (Bypass/
Charge Mode)
55–65 Hz (default)
44–70 Hz (allowable)
AC1 voltage range—Sell Mode
a
(automatically adjusts when entering Sell
Mode)
a.This unit or system is provided with fixed trip limits and shall not be aggregated above 30 kW on a single Point of
Common Connection
L-n: 108–130 ±1.5 Vac
L-L: 214–260 ±3.0 Vac
AC1 Frequency range—Sell Mode
a
(automatically adjusts when entering Sell
Mode)
59.4–60.4 ±0.05 Hz
AC Output Current (maximum 75%
imbalance between L1-n, L2-n)
L-n: 37.5 A
L-L: 25.0 A
L-n: 28.1 A
L-L: 18.8 A
L-n: 25.0 A
L-L: 16.7 A
AC Output Breaker 60 A double-pole
AC Output Frequency 60.0 ±0.1 Hz
Total Harmonic Distortion < 5%
Automatic Transfer Relay 60 A
Auxiliary Relay Output 0–12 Vdc, maximum 250 mA DC
CEC Weighted Efficiency 93.5% 93% 91%
CEC Power Rating 6,000 W 4,500 W 4,000 W
DC Input Voltage (Nominal) 50.4 Vdc 50.4 Vdc 25.2 Vdc
DC Input Voltage Range 44–64 Vdc 44–64 Vdc 22–32 Vdc
DC Current at Rated Power 127 A 95 A 171 A
Continuous Charge Rate at L-L voltage 100 A 85 A 150 A
Power Factor Corrected Charging PF (0.98)