Yamaha RCX Series Robotics User Manual


 
1
Outline
1-5
5.
Shift of CC-Link system connection status and robot controller status
Always start the CC-Link system specification robot controller in the servo OFF state
after the power is turned ON.
q Normal state of CC-Link system connection when robot controller power
is turned ON
Robot
controller
Master station
PLC
Emergency stop/interlock signal in CC-Link system are valid
When SAFE mode is enabled, service mode input signal is made valid with SI (02) in
the CC-Link system.
• Emergency stop terminal in SAFETY connector is valid.
Interlock signal in STD. DIO connector is valid when the external 24V monitor con-
trol setting in SYSTEM > PARAM mode is left valid.
• When the external 24V monitor control setting in SYSTEM > PARAM mode is left
valid while SAFE mode is enabled, service mode input signal is made valid with DI
(02) in SAFETY connector.
* The signals in the CC-Link system are sent and received.
* Always initialize with the master station PLC when connecting to the CC-Link sys-
tem.
w Shift from CC-Link system normal connection state to CC-Link sys-
tem erroneous connection state
Robot
controller
Master station
PLC
Robot
controller
Master station
PLC
Robot
controller
Master station
PLC
or
Emergency stop input turns off with SI (00) in the robot controller.
Service mode input turns off with SI (02) in the robot controller.
• Emergency stop terminal in SAFETY connector is valid.
Interlock signal in STD. DIO connector is valid when the external 24V monitor con-
trol setting in SYSTEM > PARAM mode is left valid.
• When the external 24V monitor control setting in SYSTEM > PARAM mode is left
valid while SAFE mode is enabled, service mode input signal is made valid with DI
(02) in SAFETY connector.
* The signals in the CC-Link system are not sent or received.
* The “CC-Link Communication Error” is added to the error history in the robot con-
troller.
* If the connection to the CC-Link system shifts from the normal state to the erroneous
state, the CC-Link system connection must be returned to the normal state.
* The CC-Link system will return when the CC-Link system connection is recovered to
the normal state.