Operation
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 7
Press ESC until you get to the Top-Level Status Screen, which provides you with basic
system status information.
Press Enter to open the Top-Level Menu screen. This screen is the launching pad to
command, configure, and monitor the system.
Press Up and Down to navigate the selector arrow and view all sub-menu screens.
Press Up, Down and Enter to move input arrow to select and enter
information.
ESC
Top-Level Status Screen
Chrg 100%
Load 000%
120Vin 000Vout 60Hz
Runtime: 0hr 0m
(factory default)
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
Top-Level Menu
Selector
Arrow
Bat Voltage: 215V
Bat Capacity 100.0%
Runtime: 01hr 30min
16 Batts, 00Bad
Battery Module Status Screen
Power Module Status Screen
Scroll arrows indicate additional screens
Capacity: 40.0kVA
Fault Tolerance: n+1
Total UPS Modules: 5
Bad UPS Modules: 00
Low Batt Dur: 2min
Shutdwn Dly:
Return Dly:
Return Bat Cap:
Shutdown Menu
Input arrows indicate changeable options
20sec
0sec
0%
Shutdown Menu
Low Batt Dur: 10min
Shutdwn Dly:
Return Dly:
Return Bat Cap:
20sec
0sec
0%