System Re-Start Procedure
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 37
From the Control Menu, choose Turn Load On.
Load On LED should now be lit.
If a problem is reported, ensure that the system component in question is correctly
installed. If the problem persists, refer to Basic Troubleshooting.
The UPS is now ready to support the load equipment.
If On Batt, Fault or Bypass LED is on, refer to Troubleshooting section.
Bat Voltage: 215V
Bat Capacity 100.0%
Runtime: 01hr 30min
16 Batts, 00Bad
Typical Status Screen
Turn Load On
Do Self Test
Simulate Power Fail
Graceful Reboot
Control Menu Screen
UPS Load is ON.
Confirm Menu Screen
LOAD ON
ON BATT
BYPASS
FAULT
Bad Battery Module
Fault Screen
LOAD ON
ON BATT
BYPASS
FAULT