System Re-Start Procedure
Press until you get to the Top-Level Status Screen, which provides you with basic
system status information.
Press Enter to open the Top-Level Menu screen. This screen is the launching pad to
command, configure, and monitor the system.
Press the down key and then the enter key to select Status. Verify that all power,
battery and intelligence modules are detected by the system and are functioning correctly by
scrolling down and reviewing all status screens. Please note that the intelligence modules
are monitored under the “Miscellaneous” Status Screen (submenu under Status).
Wait approximately 30 seconds for system to boot up. Display will show a fault if Power
Module Locking Latch is not engaged.
OFF
ON
Utility Power ON
Battery Enclosure
Switch ON
S
Y
S
T
E
M
E
N
A
B
L
E
System Enable
Switch ON
ESC
?
ESC
Chrg 100%
Load 000%
120Vin 000Vout 60Hz
Runtime: 00hr 0m
LOAD ON
ON BATT
BYPASS
FAULT
Top-Level Status Screen
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
Top-Level Menu