American Power Conversion PX Power Supply User Manual


 
Operation
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 11
Set-up functions
Display parameters are set to factory defaults.
Changing factory default settings:
Set-up screens
From the Setup screen, you can select the following:
Self Test
Lst Xfr
Status
IM
RIM
Status of the last self-test.
Information on the last transfer to battery operation.
General UPS status.
Status of the main intelligence module.
Status of the redundant intelligence module.
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
Top-Level Menu
Selector
Arrow
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
Top-Level Menu
Settings:
Shutdown
Defaults
Settings Menu
Output Freq
Alarms
Bypass
Copy
Other
Shutdown Configure the following system shutdown conditions:
Low Batt Dur: Low battery duration is the time from low battery signal to the
shutdown of the load. This signal is sent to the server using shutdown software
(PC + PCNS).
Shutdwn Dly: Shutdown delay is the time from when the UPS receives a
shutdown command (usually sent by a server) to the shutdown of UPS power to
the load equipment. This delay allows load equipment to finish shutdown
processes.
Return Dly: Return delay is the amount of time the UPS needs to turn on after a
power outage has ended.
Return Bat Cap: Return battery capacity is the minimum percentage of battery
capacity required for the UPS to turn the load on.
Defaults Return all UPS settings to their default values.