American Power Conversion PX Power Supply User Manual


 
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 33
Module Installation
Battery Module installation
Install Battery Units in the lowest available bay, 4 across. Position the Battery Unit to slide in
between the grooves. Push completely into the UPS to ensure connection.
WARNING!
Only APC-trained personnel familiar with the construction and operation of the
equipment, and the electrical and mechanical hazards involved, may install and
remove system components.
CAUTION!
Before installing any modules in the UPS, ensure that the System Enable Switch is left in
the STAND-BY position (if not, see Total Power OFF procedure).
At least 1 Battery Module (4 Battery Units) is required in the Battery Enclosure and the
DC Breaker must be on to start up the system. If using value-line battery cabinets, the
battery configuration will need to be entered manually through the display.