American Power Conversion SYMINIF-PD Power Supply User Manual


 
Battery Module Replacement
The following section provides the procedure for replacing a
battery module.
Removing a Battery Module
n The battery module weighs approx. 60 lbs. Two people
are required to lift and handle a battery module.
1. Remove the grill cover from in front of the module to be
replaced. Note that the module bays are labeled to corre-
spond with the PowerView.
2. Battery modules are designed with a “drop lock” that holds
them securely in the Power Array frame. Slightly lift the front
handle of the battery module, and pull it forward to the safety
stop.
3. With one person on either side of the battery module, as-
sume the full weight of the module.
4. The safety stop retaining flange passes through the notch in
the frame as the battery module is removed. See figure 8-5.
Fig 8-5 Battery Module Retaining Flange
5. If the module has failed and needs to be disposed of, return
it to the appropriate service provider, or directly to APC for
recycyling.
Note: The Battery Module contains sealed, non-spillable lead
acid batteries. These must be recycled or disposed of properly.
8-2
Chapter 8 - Module Replacement
Installing the Replacement Module
Refer to chapter 5 for the battery module installation proce-
dure.
Replacement Battery Module Verification
From the startup screen, press any key to open the top level
menu screen. Follow the sequence in figure 8-6 to insure that
the new battery module is recognized by the Power Array sys-
tem, and is functioning properly. (Status: OK).
Fig 8-6 Replacement Battery Module Verification