34006452EN/AC - Page 23
4. Start-up
4.1 System start-up
Single-unit or modular UPS
Proceed in the following order:
– close the upstream switches supplying Mains 1 and 2 power (on the LV switchboard);
– close Mains 1 input switch Q1.
The system powers up:
– red "load not protected" light on the control panel goes on,
– the rectifier/chargers automatically starts;
– close Mains 2 input Q4S:
– close inverter output switch Q5N:
– close battery circuit breaker QF1:
– open maintenance bypass switch Q3BP:
– press the inverter on button on the control panel:
green "load protected" light blinks for 3 seconds,
the inverter starts and if transfer to Mains 2 conditions are correct, the load is supplied by the inverter,
red "load not protected" light goes off,
green "load protected" light remains on, without blinking.