Compaq 9900 Network Card User Manual


 
Hitachi Lightning 9900™ User and Reference Guide 85
5.2.5 Input Voltage Tolerances
Table 5.3 lists the input voltage tolerances for the three-phase 9960. Transient voltage
conditions must not exceed +15-18% of nominal and must return to a steady-state tolerance
within of +6 to -8% of the normal related voltage in 0.5 seconds or less. Line-to-line
imbalance voltage must not exceed 2.5%. Nonoperating harmonic contents must not exceed
5%.
Table 5.3 Input Voltage Specifications for Three-Phase Power
Frequency Input Voltages (AC) Wiring Tolerance (%)
60 Hz ± 0.5 Hz 200V, 208V, or 230V three-phase three wire + ground +6% / -8%
50 Hz ± 0.5 Hz 200V, 220V, 230V, or 240V three-phase three wire + ground +6% / -8%
50 Hz ± 0.5 Hz 380V, 400V, or 415V three-phase four wire + ground +6% / -8%
Note: User input requires a 30-amp circuit breaker for three-phase power.