Setup Menu
112
Staging
For details on this feature, see 7.10.6 - Specify Staging.
Setup Operation - Staging
SETUP OPERATION BY ZONE
Select the zone for which
operation is to change
ZONE
1=ZONE 1
2=ZONE 2
3=ZONE 3
4=ZONE 4
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
SETUP OPERATION
Select operation to edit
for zone 1
OPERATION STATE
1=AUTO SEQUENCING OFF
2=STANDBY TESTING OFF
3=FAILED STANDBY N
4=HOLD DELAY 10:00
5=RESTART DELAY 00:06
6=STAGING OFF
7=RETURN TO SETUP MENU
8=RETURN TO MAIN MENU
SELECT A NUMBER:6
>STAGING FOR ZONE 1-TYPE N FOR ON, F FOR OFF
>[F]
>[N]
>TARGET VALUE(+045.0 TO +096.0).
>[+0070.0]
>[]
>SENSITIVITY.
>[+005.0]
>[]
>COMMAND SUCCESSFUL