System and Control Options
53
7.8.3 Pager Setup - Pager Number and PIN
The AC8 may be configured to dial numeric or alphanumeric pagers when an alarm is detected. You
may enter up to four pager numbers—all configured pagers will be dialed each time an alarm occurs.
For each configured pager, you must enter the pager number to be dialed and the pager’s Personal
Identification Number (PIN).
See 8.1 - AC8 Specifications for supported pager settings.
The AC8 can send numeric or alphanumeric messages to supported pagers, as shown in the following
example:
When an alarm is detected, the first pager number is dialed—up to three times, if needed. After a suc-
cessful page or three dialing attempts, the next pager number is dialed, again with three attempts as
needed, and so on for all configured pagers.
To configure a pager:
Log In and Choose Setup System
From the Main Menu, use the arrows
↑↓ to choose System and
Control, then press Enter (see 7.1 - Login for help).
Enter your password at the Login screen.
From the System and Control Menu, use the arrows
↑↓ to choose
Setup System, then press Enter .
Select a Pager to Configure
From the Setup System Menu, shown at right, use the arrows
↑↓
to
choose Setup Modem&Pagers and press Enter .
Use the arrows
↑↓ to choose Setup Pagers from the Pagers &
Modem Menu, and press Enter .
From the Select Pager Menu, choose the pager number you
want—for example, Pager Number 1—and press Enter .
Table 23 Pager dialing results
Result of Page Action Message Generated
Successful AC8 dials next configured pager.
Unsuccessful due to:
Busy signal / no answer /
no dial tone
AC8 generates message after all three redial attempts
have failed, dials next configured pager.
Unsuccessful Page
(Event Log)
General modem
communication problem
AC8 resets modem, generates message, redials pager
up to three more times.
Modem Reset
(Event Log)
No communication with
modem
(internal hardware problem)
AC8 generates messages, makes no further dialing
attempts.
Modem Internal Fault
(Active Alarm Report,
Alarm History Log)
LIEBERT TEST
DEVICE_1 ALARM
CONTACT CLOSED
2:07 PM 06/09/04
Alphanumeric pager
message example
Pager company time stamp
Setup System Menu
SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR
↑↓=NEXT =SELECT
SETUP ZONES
SETUP OUTPUTS
> SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX
Pagers & Modem Menu
> SETUP PAGERS
SETUP MODEM
↑↓=NEXT
=SELECT
Select Pager Menu
SELECT PAGER
> PAGER NUMBER 1
PAGER NUMBER 2
↑↓=NEXT =SELECT
PAGER NUMBER 3
PAGER NUMBER 4