7.10 Setup Operation
The AC8’s operation features allow you to set up a rotation sequence to
alternate which devices are operating and which are placed on
Standby, as well as test devices while in Standby mode and specify
what to do when a Standby device goes into alarm as it is powered up.
You may specify delay times after an output changes state, directing
the AC8 to wait before acknowledging inputs (hold delay time) or turn-
ing an output on or off (restart delay time). With staging, you may con-
figure the AC8 to turn a standby device on or off when an analog sensor
detects a condition above or below specified levels.
To change any operation feature:
Log In and Choose Setup System
From the Main Menu, use the arrows
↑↓ to choose System and
Control, then press Enter (see 7.1 - Login for help).
Enter your password at the Login screen.
From the System and Control Menu, use the arrows
↑↓ to choose
Setup System, then press Enter .
Select Setup Operation
From the Setup System Menu, shown at right, use the arrows
↑↓ to
choose Setup Operation and press Enter .
Select a Zone to Configure
From the Select Zone Menu, use the arrows
↑↓ to choose the zone
you want—for example, Zone_1—and press Enter .
Use the steps following Table 28 to access any of the Setup Opera-
tion options.
Table 28 shows the default settings for operation options: automatic sequencing, standby testing,
failed standby, hold delay, restart and staging.
Figure 12 provides an overview of the Setup Operation screens available via the LCD interface.
Figure 12 Menu overview - Setup Operation menu
Table 28 Default settings - operation features
Feature Default Other Options
AUTO SEQUENCING OFF (Deactivated) ON (Activated), 12h (Activated for 12-hour intervals)
STANDBY TESTING OFF (Deactivated) ON (Activated)
FAILED STANDBY N (Deactivated) Y (Activated)
HOLD DELAY 10:00 (No delay) Any time (in minutes and seconds) from 00:00 to 99:59
RESTART 00:06 (No delay) Any time (in minutes and seconds) from 00:00 to 99:59
STAGING OFF (Deactivated) ON (Activated)
Setup System Menu
SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR
↑↓=NEXT =SELECT
SETUP ZONES
SETUP OUTPUTS
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
> SETUP OPERATION
SETUP I/O MATRIX
Select Zone Menu
SELECT ZONE FOR
THE OPERATION
> ZONE 1
↑↓=NEXT =EDIT
Setup Operation Menu
> AUTO SEQUENCING OFF
STANDBY TESTING OFF
FAILED STANDBY N
↑↓=NEXT =SELECT
HOLD DELAY : 10:00
RESTART : 00:06
STAGING : OFF
Setup Operation
AUTO SEQUENCING OFF
STANDBY TESTING OFF
FAILED STANDBY N
HOLD DELAY : 10:00
RESTART : 00:06
STAGING : OFF
Auto Sequencing Standby Testing Failed Standby
AUTO SEQUENCING ON
EVERY 0
3 DAYS
AT 00:00
See
Section
7.10.1
> STANDBY TESTING ON
EVERY 0
3 DAYS
AT 00:00 FOR 10 MIN
See
Section
7.10.2
FAILED STANDBY N See
Section
7.10.3
Hold Delay Restart Staging
HOLD DELAY
10
MIN : 00 SEC
See
Section
7.10.4
RESTART DELAY
00
MIN : 06 SEC
See
Section
7.10.5
STAGING: ON
TARGET: +0070.0
SENSITIVITY: +005.0
See
Section
7.10.6
Setup Operation options