Emerson AC8 Switch User Manual


 
Setup Menu
118
Table 36 AC8 - other default settings
DEFAULT SETTINGS - operation features (FROM Table 28)
Feature Default Other Options
AUTO SEQUENCING OFF (Deactivated) ON (Activated), 12h (Activated for 12-hour intervals)
STANDBY TESTING OFF (Deactivated) ON (Activated)
FAILED STANDBY N (Deactivated) Y (Activated)
HOLD DELAY 10:00 (No delay) Any time (in minutes and seconds) from 00:00 to 99:59
RESTART 00:06 (No delay) Any time (in minutes and seconds) from 00:00 to 99:59
STAGING OFF (Deactivated) ON (Activated)
JUMPER SETTINGS
Feature Default Other Options
Digital output loss-of-power jumpers OFF - Normally Open ON - Normally Closed
NOTE: The jumper position has no effect on the contact when the AC8 has power.
12VDC/24VDC analog input jumper 24VDC Acceptable voltage for all four two-wire analog sensors
422 TERM jumper
Default: jumpered
(connected)
None—do NOT change factory default
485 TERM jumper
Default: jumpered
(connected)
None—do NOT change factory default
EPOP jumper Disabled Enable to use the EPOP input
Audible horn Enabled May be disabled via the audible horn jumper
Manual Override switch
Off (outputs controlled by
programming)
On (Turn on all output relays)
DEFAULT SETTINGS - MODEM (FROM Table 21)
Feature Default Other Options
Initialization String (InitString) ATS0=1
Any string (up to 40 characters); for international
dialing, add +GCI=xx, where xx is the country code
(except B5 countries—see Table 22)
Enable Modem Diagnostic Messages N (disable) Y (enable)
Modem Dial Prefix ATE0X4DT Any string
Modem Hang Up Delay After a Call 10 seconds Any number (up to 99 seconds)
DIP SWITCH SETTINGS
Feature Default Other Options
8-position DIP switch All are OFF (down)
May be used to reset password to factory default (see
9.9.1- Change Password)
OTHER SETTINGS
Feature Default Other Options
Change state of outputs - automatic
or manual control
AUTO (automatic control)
Force an output ON / OFF via Manual Output Ctrl menu
Force all outputs ON via hardware switch
Password AAAA Any 4 characters (see Table 14 for valid characters)
Reset common alarm with silence N (not reset) Y (reset with silence)
Battery connected Y (connected) N (not connected)