System and Control Options
35
Figure 10 Menu overview - System and Control menu
Opening Screen
LIEBERT AC8
DD-MON-YY HR:MM:SS
VX.XXX.X
PRESS ↵=STATUS/SETUP
Main Menu
VIEW STATUS
> SYSTEM AND CONTROL
↑↓=NEXT ↵=SELECT
Login Screen
LOGIN
AAAA
↑↓=SELECT ↵=NEXT/END
System & Control menu
Setup System selected
System & Control menu
Override Output selected
System & Control menu
Clear Alarms&Logs selected
> SETUP SYSTEM
OVERRIDE OUTPUT
CLEAR ALARMS & LOGS
SETUP SYSTEM
> OVERRIDE OUTPUT
CLEAR ALARMS & LOGS
SETUP SYSTEM
OVERRIDE OUTPUT
> CLEAR ALARMS & LOGS
Setup System menu Select Output Clear Alarms/Logs menu
SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR
SETUP ZONES
SETUP OUTPUTS
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX
See
Section
7.2
OVERRIDE OUTPUT
> DEVICE_1 AUTO
DEVICE_2 AUTO
.
.
.
DEVICE_8 AUTO
See
Section
7.12
CLEAR ACTIVE ALARMS
CLEAR ALARM LOG
CLEAR EVENT LOG
CLEAR TREND LOGS
See
Section
7.13
Override Output
SELECT DEVICE_1
AUTO
CLEAR ACTIVE ALARMS
ARE YOU SURE? N
CLEAR ALARM LOG
ARE YOU SURE? N
CLEAR EVENT LOG
ARE YOU SURE? N
CLEAR TREND LOGS
ARE YOU SURE? N
Setup Inputs Setup Common Alarm Setup Sensor Setup Zones Setup Outputs
SELECT INPUT
> DEVICE_1 NO-AL-L
DEVICE_2 NO-AL-L
.
.
.
DEVICE_8 NO-AL-L
See
Sec.
7.3
RESET COMMON ALARM
WITH SILENCE? N
See
Sec.
7.4
SELECT SENSOR
> SENSOR_1 +80.00 DEG
.
.
.
SENSOR_4 +79.50 RH
See
Sec.
7.5
SETUP ZONES
> ZONE 1:4
ZONE 2:0
ZONE 3:0
ZONE 4:0
See
Sec.
7.6
SELECT OUTPUT
> DEVICE_1 NO-OP-E-E
DEVICE_2 NO-ST-E-E
.
.
.
DEVICE_8 NO-NU-E-E
See
Sec.
7.7
SETUP DEVICE_1
LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
LATCHED: Y
DELAY: 00:01
SETUP SENSOR_1
CONNECTED: N
LABEL: SENSOR_1
UNITS: DEG
4 mA: +045.0
20 mA: +096.0
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
# DEVICES IN ZONE
ZONE 1:4
SETUP DEVICE_1
NORM OPEN/CLOSE: NO
MODE: OPERATING
IN ALARM: ENABLE
EMERG OP: ENABLE
Setup Modem & Pagers Setup System Info Setup Operation Setup I/O Matrix
SETUP PAGERS
SETUP MODEM
See
Sec.
7.8
CHANGE PASSWORD
CHANGE DATE & TIME
SETUP SITE ID
CONNECT BATTERY
SETUP SERV PH NUM
FACTORY DEFAULTS
See
Sec.
7.9
SELECT ZONE FOR
THE OPERATION
> ZONE 1
See
Sec.
7.10
MAP INPUT TO RELAY
MAP SENSOR TO RELAY
See
Sec.
7.11
SELECT PAGER
PAGER NUMBER 1
.
.
.
PAGER NUMBER 4
ENTER INIT STRING
ATS0=1
> AUTO SEQUENCING OFF
STANDBY TESTING OFF
FAILED STANDBY N
HOLD DELAY : 10:00
RESTART : 00:06
STAGING : OFF
SELECT INPUT
DEVICE_1
DEVICE_2
.
.
.
DEVICE_8
SELECT SENSOR
SENSOR_1 HIGH STPT
SENSOR_1 LOW STPT
.
.
.
SENSOR_4 LOW STPT
SET PAGER 1 NUMBER
SET PAGER 1 PIN
See Figure 11
for details on
Setup System Info
See Figure 12
for details on
Setup Operation
1 CONTROL RELAY
1 2
Y N
1H CONTROL RELAY
1 2
Y N
Setup System options