Emerson P/N MMI-20019808 Network Card User Manual


 
24 Micro Motion EtherNet/IP Module
Troubleshooting
5.2 Common problems
Symptom Resolution
Problem during configuration
Upload / Download.
Serial communication failed. Try again.
The Config Line LED turns red in the
Ethernet Config Tool.
Serial communication failed. Try again.
The serial port seems to be avail-
able, but it is not possible
to connect to the EtherNet/IP
Module.
The serial port may be in use by another application. Exit the EtherNet/IP Module
Configuration Tool and close all other applications, including the ones in the system
tray. Try again.
Select another serial port. Try again.
Poor performance In the Ethernet Config Tool, right-click
Sub-Network in the Navigation window and
select
Sub-Network Status to see status / diagnostic information about the Moldbus
serial network. If the EtherNet/IP Module reports a large number of re-transmissions,
check your cabling and/or try a lower baud rate setting for the Modbus serial network
(if possible).
Is the Sub-Net Monitor in the Ethernet Config Tool active? The sub-network monitor
has a negative influence on the overall performance of the gateway, and should be
used only when necessary.
Is the Node Monitor in the Ethernet Config Tool active? The node monitor has a
negative influence on the overall performance of the gateway, and should be used
only when necessary.
No Modbus serial network func-
tionality
Use the Data logger functionality of the Ethernet Config Tool to record the serial data
communication on the sub-network.
If no data is being transmitted, use the Ethernet Config Tool to check the configura-
tion.
If no data is being received, check the cables and connections. Also verify that the
transmitted data is correct.
Process variables displayed or
reported as 0
Verify the Modbus connection between the EtherNet/IP Module and the device.