FieldServer FS-8704-49 Computer Drive User Manual


 
FS-8700-49_Data_Aire_DAP Page 20 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
FieldServer
Array
Location
FieldServer Data
Field
Point Description
Message
Type
D/A Control Panel
Type
474 adj_rate Adjustment rate DAP Menu DAP049,048,046
478 alrm_delay_1
optional alarm 1 delay
setting
DAP Menu DAP049,048,046
479 alrm_delay_2
optional alarm 2 delay
setting
DAP Menu DAP049,048,046
480 alrm_delay_3
optional alarm 3 delay
setting
DAP Menu DAP049,048,046
481 alrm_enable_1
Enable optional alarm 1
for alarm relay
DAP Menu DAP049,048,046
482 alrm_enable_2
Enable optional alarm 2
for alarm relay
DAP Menu DAP049,048,046
483 alrm_enable_3
Enable optional alarm 3
for alarm relay
DAP Menu DAP049,048,046
484 alrm_select_1
Select alarm message for
Optional alarm input 1
DAP Menu DAP049,048,046
485 alrm_select_2
Select alarm message for
Optional alarm input 2
DAP Menu DAP049,048,046
486 alrm_select_3
Select alarm message for
Optional alarm input 3
DAP Menu DAP049,048,046
487 Chilled_water
Chilled water Valve
configuration
DAP Menu DAP049,048,046
488 Compressor_config Compressor configuration DAP Menu DAP049,048,046
489 c_mode
Unit in Centigrade
temperature mode?
DAP Menu DAP049,048,046
490 fire_lim
Firestat temperature
setting
DAP Menu DAP049,048,046
491 heat_strip_config Heating configuration DAP Menu DAP049,048,046
492 hi_cal A to D high limit setting DAP Menu DAP049,048,046
493 hi_h_limit
High humidity alarm limit
setting
DAP Menu DAP049,048,046
494 hi_t_lim
High temperature alarm
limit setting
DAP Menu DAP049,048,046
495 humid_config Humidifer configuration DAP Menu DAP049,048,046
496 h_calib Humidity calibration offset DAP Menu DAP049,048,046
497 lead_lag
Compressor lead/lag
setting
DAP Menu DAP049,048,046
498 loc_h_ddband humidity deadband setting DAP Menu DAP049,048,046
499 loc_h_setpt Humidity setpoint DAP Menu DAP049,048,046
500 loc_t_dband
Temperature deadband
setting
DAP Menu DAP049,048,046
501 loc_t_setpt Temperature setpoint DAP Menu DAP049,048,046
502 lo_cal A to D low limit setting DAP Menu DAP049,048,046
503 lo_h_lim
Low humidity alarm limit
setting
DAP Menu DAP049,048,046
504 lo_t_lim
Low temperature alarm
limit setting
DAP Menu DAP049,048,046
505 main_int
Maintenance schedule
setting
DAP Menu DAP049,048,046
506 passwd_a Password A setting DAP Menu DAP049,048,046
507 passwd_b Password B setting DAP Menu DAP049,048,046