Byte
Bit
Relative
Offset
Location in
Data Array
(Absolute
Offset) Each
alarm stored as
a separate bit
Location in
Data
Array
(Absolute
Offs
et) Each set
of 8 alarms
stored as a
byte*
046, 048 and 049 Units DAP 80 Units
3 0
24 97 46:00
Low air temperature
warning
Local alarm #1: See
tag inside door
3 1
25 98 46:01
High air temperature
warning
Local alarm #2: See
tag inside door
3 2
26 99 46:02 Low Humidity warning
Local alarm #3: See
tag inside door
3 3
27 100 46:03 High Humidity warning
Local alarm #4: See
tag inside door
3 4
28 101 46:04 Low chilled-water-in alarm
Standby pump on:
check primary pump
3 5
29 102 46:05
High chilled-water-in
alarm
UPS power on:
check main power
supply
3 6
30 103 46:06
Low chilled-water-out
alarm
Custom message on
optional input #1
3 7
31 104 46:07
High chilled-water-out
alarm
Custom message on
optional input #2
4 0
32 105 47:00
High or Low limits
misadjusted
Custom message on
optional input #3
4 1
33 106 47:01
Air temperature sensor
error
Custom message on
optional input #4
4 2
34 107 47:02 Humidity sensor error
Humidification
Inhibited
4 3
35 108 47:03 Discharge air sensor error
Reheat inhibited
4 4
36 109 47:04
No communications with
temp/humid module
Reheat and
humidification
inhibited
4 5
37 110 47:05
No communications with
LCD module
Discharge air
temperature limit
(just a condition)
4 6
38 111 47:06
Alarm network
communications failure
Reheat mode during
dehumidification
(just a condition)
4 7
39 112 47:07
AC Power or controller
restart
Manual Override:
Check bypass
switches (DAPII ver
5.1 and later)
5 0
40 113 48:00
Network doppelganger
error
N/A
5 1
41 114 48:01
Incompatible Fahrenheit /
centigrade mode
N/A
5 2
42 115 48:02
Schedule normal
maintenance due
N/A
5 3
43 116 48:03
compressor short cycle
warning
N/A
5 4
44 117 48:04
Fan motor overload,
check motor amperage
N/A