FieldServer FS-8704-49 Computer Drive User Manual


 
FS-8700-49_Data_Aire_DAP Page 21 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
FieldServer
Array
Location
FieldServer Data
Field
Point Description
Message
Type
D/A Control Panel
Type
508 rst_mode Restart mode setting DAP Menu DAP049,048,046
509 s_delay
Start delay setting (in
seconds)
DAP Menu DAP049,048,046
510 t_calib
Temperature calibration
offset
DAP Menu DAP049,048,046
511 voice Audible alarm tone setting DAP Menu DAP049,048,046
512 vvrg
Chilled water output
voltage setting
DAP Menu DAP049,048,046
513 cat1
Alarm relay #1 category
selection
DAP Menu DAP 046
514 cat2
Alarm relay #2 category
selection
DAP Menu DAP 046
515 cat3
Alarm relay #3 category
selection
DAP Menu DAP 046
516 d_calib
Discharge Air sensor
calibration offset
DAP Menu DAP 046
517 lo_d_lim
Low Discharge
temperature limit setting
DAP Menu DAP 046
518 ptc
Person to contact on
alarm message
DAP Menu DAP 046
All the points of Chiller Panel are omitted from this list
899 adj_rate Adjustment rate setting DAP80 Menu DAP80
900 alrm_delay_1
optional alarm 1 delay
setting
DAP80 Menu DAP80
901 alrm_delay_2
optional alarm 2 delay
setting
DAP80 Menu DAP80
902 alrm_delay_3
optional alarm 3 delay
setting
DAP80 Menu DAP80
903 alrm_delay_4
optional alarm 4 delay
setting
DAP80 Menu DAP80
904 alrm_select_1
Select alarm message for
Optional alarm input 1
DAP80 Menu DAP80
905 alrm_select_2
Select alarm message for
Optional alarm input 2
DAP80 Menu DAP80
906 alrm_select_3
Select alarm message for
Optional alarm input 3
DAP80 Menu DAP80
907 alrm_select_4
Select alarm message for
Optional alarm input 4
DAP80 Menu DAP80
908 ant_enable
Humidity anticipation
setting (on/off)
DAP80 Menu DAP80
909 autoflush_time Autoflush timer setting DAP80 Menu DAP80
910 auto_ack
Automatic self-test
acknowledge
DAP80 Menu DAP80
911 Comp_config Compressor configuration DAP80 Menu DAP80
912 control_type Control type setting DAP80 Menu DAP80
913 c_mode
display temperature mode
(F or C degree)
DAP80 Menu DAP80
914 DA_volts
Water Valve voltage range
setting
DAP80 Menu DAP80
915 dehum_on
Dehumidification mode
selection
DAP80 Menu DAP80