FieldServer FS-8704-49 Computer Drive User Manual


 
FS-8700-49_Data_Aire_DAP Page 37 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
Message Description Discussion
DAP:#25
Err. Field= <%s>
cannot be used for
write. Map Descriptor=
<%s>
This error arises when (1) a Map Descriptor refers to a
field that is not unique but the function has not been
specified or (2) when a non-writeable field has been
specified. See section 4.4.5 for additional information.
This error could also be produced if there are two (or
more) write Map Descriptors each having a different
DA_Func but with the DA_Assoc values of each Map
Descriptor set equal (or implied equal when not set in
the csv file). Specify the DA_Assoc parameter for the
write Map Descriptor’s, ensuring that non-associated
Map Descriptor’s have different values for this
parameter.
7
DAP:#26
Err. Map Descriptor=
<%s> Read: param-
>daire_function= %c
DAP:#27
Err. Cant write.
function= %d Map
Descriptor= <%s>
You are trying to a read/write data from a DAP device
and the driver cannot process the specified
DA_Function for reading.
7
DAP:#28!
Err. No Map
Descriptor’s
Report this error to FST providing a copy of your CSV
file.
DAP:#29
Err. Map Descriptor=
<%s> Special
specified with invalid
method.
DAP:#30
Err. Map Descriptor=
<%s> Unknown
translation Method=
%d
Read Appendix B.4 and review the CSV file. When you
have corrected the CSV file reset the FieldServer for the
changes to take effect.
DAP:#31
Err. Cant translate
map desc. Data not
stored
Make a log file and report the problem to FST providing
a copy of your CSV file.
DAP:#32
Err. Driver does not
support unit type='%c'
( node= %d)
The driver found a device whose type is not supported.
Remove this node from your CSV file and reset the
FieldServer
DAP:#33
Err. Conflicting unit
types='%c' vs '%c' (
node= %d)
The expected and discovered unit type are different.
The driver will always work with the discovered unit
type.
DAP:#35
Err. Cant write to a
data logger Map
Descriptor= <%s>
Correct the problem by removing the offending map
desc and reset the FieldServer for the change to take
effect
DAP:#36
FYI. Can’t write until
unit type is known. Will
retry. Map Descriptor=
<%s>
This message is printed when you have specified a
write with a DA_Field but no DA_Function. Under these
circumstances the driver cannot write until it knows the
Unit Type of the device. If you are polling using the
‘Everything’ function then the driver will obtain the unit
type in time and the error will not be reproduced.
7