FieldServer FS-8704-49 Computer Drive User Manual


 
FS-8700-49_Data_Aire_DAP Page 44 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
Byte
Bit
Relative
Offset
Location in
Data Array
(Absolute
Offset) Each
alarm stored as
a separate bit
Location in
Data
Array
(Absolute
Offs
et) Each set
of 8 alarms
stored as a
byte*
046, 048 and 049 Units DAP 80 Units
5 5
45 118 48:05
Custom message on
optional alarm input #1
N/A
5 6
46 119 48:06
Custom message on
optional alarm input #2
N/A
5 7
47 120 48:07
Custom message on
optional alarm input #3
N/A
6 0
48 121 49:00
Discharge air temperature
limit (just a condition)
N/A
6 1
49 122 49:01
Reheat mode during
dehumidification (just a
condition)
N/A
6 2
50 123 49:02 N/A N/A
6 3
51 124 49:03 N/A N/A
6 4
52 125 49:04 N/A N/A
6 5
53 126 49:05 N/A N/A
6 6
54 127 49:06 N/A N/A
6 7
55 128 49:07 N/A N/A
Notes
*
43:00 Indicates array
element zero. Individual
alarm can be found by
masking and looking at
the zero'th bit of this
element.
Chiller Stat Query
Unlike the Dap-Stat errors, these are stored in the Data Array using only one method
each error is stored at a separate location in the Data Array.
Location in Data Array
(Absolute Offset) Each alarm
stored as a separate bit
Alarm / Bit Descriptions Byte
Bit
Relative
Offset
536 Auxiliary cooling available 0 0
0
537 Auxiliary cooling locked out 0 1
1
538 Unit on backup module standby 0 2
2
539 Custom message on optional input #1 0 3
3
540 Custom message on optional input #2 0 4
4
541 Evaporator freeze stat module #1 0 5
5
542 Evaporator freeze stat module #2 0 6
6
543 Evaporator freeze stat module #3 0 7
7
544 High pressure problem module #1 1 0
8
545 High pressure problem module #2 1 1
9
546 High pressure problem module #3 1 2
10
547 High return temperature warning 1 3
11
548 High supply temperature warning 1 4
12
549 Local alarm #1: See tag inside door 1 5
13