4.2. Client Side Connection Descriptions
Connections
Column Title Function Legal Values
Port
This is the FieldServer port
connected to the DART’s RS-
232 port.
P1-P8, R1-R2
1
(P1-P8) requires 232/485
converter.
Secondary_Port*
The return loop from the DAP
devices is connected to this
port. (Loop connected to Tx+
& Tx- terminals.
P1-P8, R1-R2
1
(R1-R2) requires 232/485
converter.
Baud* Specify baud rate
2400/9600
2
(Vendor
Limitation)
Parity* Specify parity
None
Data_Bits*
Specify data bits
8
Stop_Bits*
Specify stop bits
1
Protocol
Specify protocol used. Either
keyword may be used.
DAP, Daire
Handshaking*
Specify hardware
handshaking
None
Poll Delay*
Time between internal polls
0-32000s, 1s
Example
// Client Side Connections
Connections
Port,
Secondary Port, Protocol, Baud,
Parity, Data_Bits, Stop_Bits, Poll_Delay
R1, R2, DAP, 2400, None, 8, 1, 0.100s
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.
2
DAP V9.5 or later supports 9600
Use this port identifier in the client side node
configuration described in Section 4.3.