FieldServer FS-8704-49 Computer Drive User Manual


 
FS-8700-49_Data_Aire_DAP Page 27 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
Appendix B.2. DA_Func Parameter - Permitted values.
The driver supports a limited subset of the Dart Poll & Response Functions. The selection
of the sub-set is based on the identification of useful & practical functions.
In addition to the ‘Everything’ keyword indicated in chapter 4 the following specific query
functions are implemented.
Func. Description Driver Parameter Protocol Id.
‘1’ DART Config Query DA_Func = dart-config 49
‘2’ Dart Psswd Query DA_Func = dart-password 50
'3' DAP Config Command DA_Func = dap-config 51
'4' DAP Log Query DA_Func = dap-log 52
'5' DAP Unit-Type Query DA_Func = dap-unit 53
'6' DAP Stat Query DA_Func = dap-stat 54
'7' DAP Xtra Query DA_Func = dap-xtra 55
'8' DAP Menu Query DA_Func = dap-menu 56
'A' Chiller Stat Query DA_Func = chiller-stat 65
'B' Chiller Xtra Query DA_Func = chiller-xtra 66
'C' Chiller Menu Query DA_Func = chiller-menu 67
‘D Dart Status DA_Func = dart-status 68
'E' DAP80 Menu Query DA_Func = dap80-menu 69
'G' DAP Analog Query DA_Func = dap80-analog 71
'H' DAP Channels Query DA_Func = dap80_channles 72
Each of the above queries returns a complex set of data consisting of many sub-fields.
Contact Data-Aire for a complete listing of the data composite returned.
The following special / diagnostic functions are also implemented.
Driver Parameter Protocol Id.
DA_Func = All-Listen 11
DA_Func = Ack 6
DA_Func = Dart-Transparant 2
DA_Func = Dart-Opaque 3
DA_Func = Test-Echo 16
DA_Func = Test-No-Echo 15
DA_Func = Unit-Talk 13
With the exception of the Unit-Talk transmission of this command, these are nodeless
commands to allow the units time to switch their mechanical command. When using any of
these special commands no other DA_* fields need be specified.
All-Listen instructs the all units in the network to switch their relays to the listen position.
Those units already in the listen position will do nothing. Those in the talk position will first
echo the all-listen command and then switch their relays to the listen position. A pause of
0.15 seconds is required after the relays.