Byte
Bit
Relative
Offset
Location in
Data Array
(Absolute
Offset) Each
alarm stored as
a separate bit
Location in
Data
Array
(Absolute
Offs
et) Each set
of 8 alarms
stored as a
byte*
046, 048 and 049 Units DAP 80 Units
0 4
4 77 43:00
High Pressure Failure
Compressor No. 4
Humidifier problem:
check water
pressure
0 5
5 78 43:01
High Pressure Warning
Compressor No. 1
Low voltage
warning: check unit
0 6
6 79 43:02
High Pressure Warning
Compressor No. 2
Firestat alarm: unit
shutdown
0 7
7 80 43:03
High Pressure Warning
Compressor No. 3
Compressor short
cycle warning
1 0
8 81 46:00
High Pressure Warning
Compressor No. 4
Power problem or
unit restart
1 1
9 82 46:01
Low Pressure Failure
Compressor No. 1
Humidity sensor
problem
1 2
10 83 46:02
Low Pressure Failure
Compressor No. 2
Temperature sensor
problem
1 3
11 84 46:03
Low Pressure Failure
Compressor No. 3
Scheduled
maintenance due
1 4
12 85 44:04
Low Pressure Failure
Compressor No. 4
High pressure C1:
Manual reset
required
1 5
13 86 44:05
No Air Flow, Check Belt
and motor
Low pressure C1:
Manual reset
required
1 6
14 87 44:06
Change Filters, High
Pressure Drop
High pressure C2:
Manual reset
required
1 7
15 88 44:07
Local Alarm. See Tag
inside Door
Low pressure C2:
Manual reset
required
2 0
16 89 45:00
Manual Override, service
or emergency
Smoke detector: unit
shutdown
2 1
17 90 45:01
Humidifier Failure, Check
water pressure
No water flow: check
pump
2 2
18 91 45:02
No water flow. Check
glycol pump.
Discharge
temperature sensor
problem
2 3
19 92 45:03
Smoke detected, located
inside unit
High temperature
warning
2 4
20 93 45:04
Fire Stat Tripped, Location
inside unit
Low temperature
warning
2 5
21 94 45:05
Standby pump on, check
glycol pump
High humidity
warning
2 6
22 95 45:06
Low voltage warning,
check unit
Low humidity
warning
2 7
23 96 45:07
Water detected in under
floor area
Fan motor overload:
check motor
amperage