FieldServer FS-8704-49 Computer Drive User Manual


 
FS-8700-49_Data_Aire_DAP Page 45 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
Location in Data Array
(Absolute Offset) Each alarm
stored as a separate bit
Alarm / Bit Descriptions Byte
Bit
Relative
Offset
550 Local alarm #2: See tag inside door 1 6
14
551 Low pressure problem module #1 1 7
15
552 Low pressure problem module #2 2 0
16
553 Low pressure problem module #3 2 1
17
554 Low return temperature warning 2 2
18
555 Low supply temperature warning 2 3
19
556 Low voltage warning: check unit 2 4
20
557 Scheduled normal maintenance due 2 5
21
558 Manual override: compressor 2 6
22
559 Manual override: check bypass switches 2 7
23
560 No chilled water flow module #1 3 0
24
561 No chilled water flow module #2 3 1
25
562 No chilled water flow module #3 3 2
26
563 No condenser water flow 3 3
27
564 Power problem or restart 3 4
28
565 Return temperature sensor problem 3 5
29
566 compressor short cycle warning 3 6
30
567 Standby pump on: Check primary pump 3 7
31
568 Supply temperature sensor problem 4 0
32
569 Unit on total standby 4 1
33
570 Under floor water detected 4 2
34
571 N/A 4 3
35
572 N/A 4 4
36
573 N/A 4 5
37
574 N/A 4 6
38
575 N/A 4 7
39
576 N/A 5 0
40
577 N/A 5 1
41
578 N/A 5 2
42
579 N/A 5 3
43
580 N/A 5 4
44
581 N/A 5 5
45
582 N/A 5 6
46
583 N/A 5 7
47