FieldServer FS-8704-49 Computer Drive User Manual


 
FS-8700-49_Data_Aire_DAP Page 22 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
FieldServer
Array
Location
FieldServer Data
Field
Point Description
Message
Type
D/A Control Panel
Type
916 d_calib
Discharge Air sensor
calibration offset
DAP80 Menu DAP80
917 esaver_supp_comp
Energy saver supplement
mode setting
DAP80 Menu DAP80
918 fire_lim
Firestat temperature limit
setting
DAP80 Menu DAP80
919 heater_config Heating configuration DAP80 Menu DAP80
920 hi_h_lim
High humidity alarm limit
setting
DAP80 Menu DAP80
921 hi_t_lim
High temperature alarm
limit setting
DAP80 Menu DAP80
922 humid_config Humidifier configuration DAP80 Menu DAP80
923 h_calib Humidity calibration offset DAP80 Menu DAP80
924 h_dband humidity deadband setting DAP80 Menu DAP80
925 lead_lag
Compressor lead/lag
setting
DAP80 Menu DAP80
926 lo_d_lim
Low Discharge
temperature limit setting
DAP80 Menu DAP80
927 lo_h_lim
Low humidity alarm limit
setting
DAP80 Menu DAP80
928 lo_t_lim
Low temperature alarm
limit setting
DAP80 Menu DAP80
929 main_int
Maintenance schedule
setting
DAP80 Menu DAP80
930 network_id set unit Network ID DAP80 Menu DAP80
931 nom_h_setpt Humidity setpoint DAP80 Menu DAP80
932 password password DAP80 Menu DAP80
933 ptc
Person to contact on
alarm message
DAP80 Menu DAP80
934 relay_1_mask_0 selection for alarm contact DAP80 Menu DAP80
950 relay_1_mask_1 selection for alarm contact DAP80 Menu DAP80
966 relay_1_mask_2 selection for alarm contact DAP80 Menu DAP80
982 relay_2_mask_0 selection for alarm contact DAP80 Menu DAP80
998 relay_2_mask_1 selection for alarm contact DAP80 Menu DAP80
1014 relay_2_mask_2 selection for alarm contact DAP80 Menu DAP80
1030 relay_3_mask_0 selection for alarm contact DAP80 Menu DAP80
1046 relay_3_mask_1 selection for alarm contact DAP80 Menu DAP80
1062 relay_3_mask_2 selection for alarm contact DAP80 Menu DAP80
1078 reverse_valve
Chilled water direction
setting
DAP80 Menu DAP80
1079 rst_mode Restart mode setting DAP80 Menu DAP80
1080 sc_alarms
Compressor short cycle
setting
DAP80 Menu DAP80
1081 s_delay
Start delay setting (in
seconds)
DAP80 Menu DAP80
1082 t_calib
Temperature calibration
offset
DAP80 Menu DAP80
1083 t_dband
Temperature deadband
setting
DAP80 Menu DAP80
1084 t_setpt Temperature setpoint DAP80 Menu DAP80