IBM 9179-MHB Power Supply User Manual


 
6. Click Close Event.
7. Add comments for the serviceable event. Include any unique additional information. Click OK.
8. Did you replace, add, or modify a field replaceable unit (FRU) of the open service action event?
v No: Select the No FRU Replaced for this Serviceable Event option, and click OK to close the
service action event.
v Yes: Perform the following steps:
a. From the FRU list, select a FRU that you need to update.
b. Double-click the FRU and update the FRU information.
c. Click OK to close the service action event.
9. If you continue to have problems, contact your service provider.
Activating and deactivating LEDs by using the HMC:
Use this procedure to activate or deactivate LEDs using Service Focal Point for the Hardware
Management Console (HMC).
Choose from the following:
v “Deactivating a system attention LED or partition LED”
v “Activating or deactivating identify LED”
Deactivating a system attention LED or partition LED:
You can deactivate a system attention LED or a logical partition LED. For example, you might determine
that a problem is not a high priority and decide to repair the problem at a later time. However, you want
to be alerted if another problem occurs, so you must deactivate the system attention LED so that it can be
activated again if another problem occurs.
1. In the navigation area, open Systems Management.
2. Open Servers and select the appropriate system.
3. In the content area, check the box for the appropriate Partition.
4. Select Tasks, then Operations, and then Manage Attention LED.
5. Select the appropriate Partition.
6. Select Deactivate System Attention LED from the Action menu. A confirmation window is displayed
that provides the following information:
v A verification that the system attention LED was deactivated.
v An indication that there still might be open problems within the system.
v An indication that you cannot activate the system attention LED.
7. Select one of the logical partitions in the lower table, and select Deactivate partition LED from the
Partition Operations menu. A confirmation window is displayed that provides the following
information:
v A verification that the logical partition LED was deactivated.
v An indication that there still might be open problems within the logical partition.
v An indication that you cannot activate the logical partition LED.
Activating or deactivating identify LED:
The system provides several LEDs that help identify various components, such as enclosures or field
replaceable units (FRUs), in the system. For this reason, they are called identify LEDs.
You can activate or deactivate the following types of identify LEDs:
Power supplies 67