Mitsubishi Electronics 700 Series Power Supply User Manual


 
16
Device Map
Special registers for control
D9148
Inverter operation
status control
Turn on/off the corresponding bits to control the
inverter operation status.
The initial value: All "0". When M9255 is off, this
device does not function.
31
D9149
Inverter operation
status control
enable/disable
setting
Enable/disable the inverter operation status control
using D9148 and M9200 to M9211 by turning on/off
the corresponding bits.
Bit image is the same as D9148.
The initial value: All "0" (invalid)
32
D9150
Inverter
parameter
access error
Stores the error No. when an error occurs because
the data stored in the parameter or special register is
not reflected on the inverter.
33
D9151 Inverter status
Stores the running status and operating status of the
inverter.
33
D9152
Frequency
setting
0.01Hz units
D9153
Running speed 1(0.1)r/min unit
D9154
Motor torque
0.1% units
D9155
Converter output
voltage
0.1V units
D9156
Regenerative
brake duty
0.1% units
D9157
Electronic thermal
relay function load
factor
0.1% units
D9158
Output current
peak value
0.01A/0.1A units
Number Name Description Page
B15 B12B11 B8B7 B4B3 B0
0:OFF
1:ON
STF
STR
RH
RM
RL
JOG
RT
AU
CS
MRS
STOP
RES
Invalid
B15 B8B7 B4B3 B0
0:OFF
1:ON
Inverter running(RUN)
Forward running
Reverse running
Up to frequency(SU)
Overload alarm(OL)
Instantaneous power failure
/undervoltage(IPF)
Output frequency
detection(FU)
Alarm output(ALM)
Minor fault output(LF)