Mitsubishi Electronics 700 Series Power Supply User Manual


 
53
CC-Link I/O Specifications
2
CC-Link COMMUNICATION
("n" indicates a value determined according to the station number setting.)
*1 Signal names are initial values. Using Pr. 180 to Pr. 186, Pr. 188, and Pr .189, you can
change input signal functions.
Signals of the RYn0, RYn1, and RYn9 can not be changed. Even when changed using Pr.
178, Pr. 179, and Pr. 187, the settings are invalid.
Refer to the inverter manual (applied) for details of Pr. 178 to Pr.189.
*2 Signal names are initial values. Using Pr. 190 to Pr .196, you can change output signal
functions.
Refer to the inverter manual (applied) for details of Pr. 190 to Pr.196.
(2) Remote resister
("n" indicates a value determined according to the station number setting.)
PLC function
device No.
Address
Description
PLC function
device No.
Address Description
Upper 8
Bits
Lower 8
Bits
RWwn
Monitor
code 2
Monitor
code 1
RWrn First monitor value
RWwn+1
Set frequency (0.01Hz
increments)
RWrn+1
Second monitor
value
RWwn+2
Link
parameter
expansion
setting
Instruction
code
RWrn+2
Reply
code2
Reply
code1
RWwn+3 Write data RWrn+3 Read data
D9062 RWwn+4
Registers designed to
read data received
from the master
station
D9078 RWrn+4 Registers designed
to write data to be
sent to the master
station.
D9063 RWwn+5 D9079 RWrn+5
D9064 RWwn+6 D9080 RWrn+6
D9065 RWwn+7 D9081 RWrn+7