System Configuration
POINT
The difference between CC-Link communication (Pr. 544 = 100, 112, 114, 118)
with PLC function and normal CC-Link communication (Pr. 544 =1, 2, 12, 14, 18)
is indicated below.
I/O (RX, RY)
I/O (RX, RY)
RWw RWr
RWw RWr
PLC CPU
CC-Link master module
Inverter
Pr.544=0,1,12,14,18
Inverter CPU
Parameter read/write, monitor, operation commands,
etc. have been assigned in advance.
PLC CPU
CC-Link master module
Pr.544=100,112,114,118
Built-in CC-Link module
Inverter
Built-in
sequence
program
User
assignment
Inverter CPU
Using built-in sequence program, parameters,
monitor, etc. must be assigned.
Other data read/write, etc. can be assigned
freely as user areas.
*Operation and speed commands have
been assigned in advance.