Mitsubishi Electronics 700 Series Power Supply User Manual


 
68
Operation Processing Method of PLC Function
3.5 Operation Processing Method of PLC Function
The operation processing method is the repeated operation of a stored program.
(1) Stored program system
1) In a stored program system, a sequence program to be operated is stored in
the internal memory beforehand.
2) When sequence program operation is executed, the sequence program stored
in the built-in PLC function is read to the CPU instruction by instruction to
execute the operation, and the corresponding devices are controlled according
to the results.
(2) Repeated operation system
In a repeated operation system, a sequence of operations is repeated.
The built-in PLC function repeats the following processings.
1) The built-in PLC function executes the sequence program stored in the
internal memory from step 0 in due order.
2) When the END instruction is executed, internal processings, such as timer/
counter present value updating and self-diagnostic checks, are performed, and
the execution returns to step 0 of the sequence program again.
Fig 3.5 Operation Processing Method of Built-in PLC Function
REMARKS
A processing from step 0 to next step 0 or from END to next END is called one scan.
Therefore, one scan is the sum of the processing time of a user-created program (step 0 to
END) and the internal processing time of the built-in PLC function.
Step 0
Step 1
Step 2
END
Built-in sequence function repeats
this operation.
Timer/counter present
value updating
Self-diagnostic
checks, etc.