Mitsubishi Electronics 700 Series Power Supply User Manual


 
33
Inverter Status Monitoring, Special Registers
for Control
1
PLC FUNCTION
1.7.5 Inverter parameter access error (D9150)
If any value outside the setting range is written during parameter write, set frequency
write, parameter clear, etc. from the sequence program of the inverter, or if write is
performed when write is disabled, a write alarm occurs and the corresponding alarm
code is stored into D9150.
<Parameter>
The parameter No. + H8000 is stored into D9150.
Example: If an error occurs during write of Pr.0 Torque boost, H8000 (H0 + H8000) is
stored into D9150.
If an error occurs during write of Pr.10 DC injection brake operation frequency,
H800A is stored into D9150.
<Operation mode, set frequency, alarm definition batch clear, all parameter
clear>
HFFFF is stored into D9150. (Normal 0)
1.7.6 Inverter status (D9151)
The running status and operating status of the inverter are stored.
The corresponding bits are set according to the inverter status.
Device No. Name
Data Access Enable
Condition
D9150 Inverter parameter access error Always
POINT
If write is completed normally after error occurrence, D9150 is not cleared
(D9150 data is held at error occurrence). When using D9150 to stop operation,
etc., the user must clear it.
Device No. Name
Data Access Enable
Condition
D9151 Inverter status Always
B15 B8B7 B4B3 B0
0:OFF
1:ON
Inverter running(RUN)
Forward running
Reverse running
Up to frequency(SU)
Overload alarm(OL)
Instantaneous power failure
/undervoltage(IPF)
Output frequency
detection(FU)
Alarm output(ALM)
Minor fault output(LF)