11 - 27 11 - 27
MELSEC-Q
11 TROUBLESHOOTING
Error Code List (Continued)
LED Status
Error Code
(SD0)
1
Error Messages
Common
Information
(SD5 to 15)
1
Individual
Information
(SD16 to 26) 1
RUN ERROR
Operating
Statuses of
CPU
Diagnostic Timing
2401 FILE SET ERROR File name Parameter number Off Flicker Stop At power ON/At reset
2410
2411
2412
2413
FILE OPE. ERROR File name Program error location Off/On Flicker/ON
Stop/
Continue
2
When instruction is executed
2500
2501
2502
2503
2504
CAN'T EXE. PRG. File name ——— Off Flicker Stop At power ON/At reset
3000
3001
3002
PARAMETER ERROR File name Parameter number Off Flicker Stop
At power ON/Reset/
STOP
RUN
PARAMETER ERROR File name/drive name Parameter number Off Flicker Stop
When an END instruction is
executed.
3003
PARAMETER ERROR File name Parameter number Off Flicker Stop
At power ON/Reset/
STOP
RUN
3004 PARAMETER ERROR File name Parameter number Off Flicker Stop
At power ON/Reset/
STOP
RUN
3006 PARAMETER ERROR File name Parameter number Off Flicker Stop
At power ON/Reset/
STOP
RUN
3009
3010
3012
3013
PARAMETER ERROR File name/drive name Parameter number Off Flicker Stop
At power ON/Reset/
STOP
RUN
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.
2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)