Mitsubishi Electronics Q12HCPU Electronic Accessory User Manual


 
11 - 25 11 - 25
MELSEC-Q
11 TROUBLESHOOTING
Error Code List (Continued)
LED Status
Error Code
(SD0)
1
Error Messages
Common
Information
(SD5 to 15)
1
Individual
Information
(SD16 to 26) 1
RUN ERROR
Operating
Statuses of
CPU
Diagnostic Timing
2110
2111
SP. UNIT ERROR Unit/module No. Program error location Off/On Flicker/On
Stop/
Continue
2
When instruction executed.
2112 Unit/module No.
2113
SP. UNIT ERROR
FFFF
H
(fixed)
Program error location Off/On Flicker/On
Stop/
Continue
2
When instruction executed/
STOP RUN
2114
2115
2116
2117
SP. UNIT ERROR Unit/module No. Program error location Flicker/On Flicker/On
Continue/
Stop
When instruction is executed
2120
2121
2122
2124
2125
SP. UNIT LAY ERR. ——— ——— Off Flicker Stop At power ON/At reset
2126 SP. UNIT LAY ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset
2150 SP. UNIT VER. ERR. Unit/module No. ——— Off Flicker Stop At power ON/At reset
2200 MISSING PARA. Drive Name ——— Off Flicker Stop At power ON/At reset
2210 BOOT ERROR Drive Name ——— Off Flicker Stop At power ON/At reset
2300
2301
2302
ICM. OPE. ERROR Drive Name ——— Off/On Flicker/On
Stop/
Continue
2
When memory card is inserted or
removed
2400 FILE SET ERROR File name Parameter number Off Flicker Stop At power ON/At reset
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.
2 The CPU module operation status when an error occurs can be set at the parameters. (LED display will change accordingly.)