Mitsubishi Electronics Q12HCPU Electronic Accessory User Manual


 
11 - 95 11 - 95
MELSEC-Q
11 TROUBLESHOOTING
Special Register List (Continue)
ACPU
Special
Conversion
Special
Register after
Conversion
Special
Register for
Modification
Name Meaning Details
Corresponding
CPU
D9216 SD1216
Stores conditions
for up to numbers
1 to 16
D9217 SD1217
Stores conditions
for up to numbers
17 to 32
D9218 SD1218
Stores conditions
for up to numbers
33 to 48
D9219 SD1219
Local station
error detect
status
Stores conditions
for up to numbers
49 to 64
Station numbers of local stations that have detected
errors are stored into corresponding data register bits as
indicated below.
SD1216
SD1217
SD1218
SD1219
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
L16 L15 L14 L13 L12 L11
L32 L31 L30 L29 L28 L27
L48 L47 L46 L45 L44 L43
L64 L63 L62 L61 L60 L59
L26
L42
L58
L25
L41
L57
L24
L40
L56
L23
L39
L55
L22
L38
L54
L21
L37
L53
L20
L36
L52
L19
L35
L51
L18
L34
L50
L17
L33
L49
L10L9L8L7L6L5L4L3L2L1
Bit
Device
number
If a local station detects an error, the bit corresponding to
the station number becomes "1".
Example: When station 6 and 12 detect an error, bits 5
and 11 in SD1216 become "1", and when
SD1216 is monitored, its value is "2080
(820
H
)".
D9220 SD1220
Stores conditions
for up to numbers
1 to 16
D9221 SD1221
Stores conditions
for up to numbers
17 to 32
D9222 SD1222
Stores conditions
for up to numbers
33 to 48
D9223 SD1223
Local station
parameters
non-conforming;
remote I/O
station I/O
allocation error
Stores conditions
for up to numbers
49 to 64
Stores the local station numbers that have mismatches
between the parameters of the master station of tier three
and those of the master station in tier two in the three tier
system or the remote I/O station numbers that have
incorrect I/O assignment, as shown below in
correspondence with the data register bits.
SD1220
SD1221
SD1222
SD1223
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
L16 L15 L14 L13 L12 L11
L32 L31 L30 L29 L28 L27
L48 L47 L46 L45 L44 L43
L64 L63 L62 L61 L60 L59
L26
L42
L58
L25
L41
L57
L24
L40
L56
L23
L39
L55
L22
L38
L54
L21
L37
L53
L20
L36
L52
L19
L35
L51
L18
L34
L50
L17
L33
L49
L10L9L8L7L6L5L4L3L2L1
Bit
Device
number
If a local station acting as the master station of tier three
detects a parameter error or a remote station contains an
invalid I/O assignment, the bit corresponding to the
station number becomes "1".
Example: When local station 5 and remote I/O station
14 detect an error, bits 4 and 13 in SD1220
become "1" , and when SD1220 is monitored,
its value is "8208 (2010
H
) " .
D9224 SD1224
Stores conditions
for up to numbers
1 to 16
D9225 SD1225
Stores conditions
for up to numbers
17 to 32
D9226 SD1226
Stores conditions
for up to numbers
33 to 48
D9227 SD1227
Local station
and remote I/O
station initial
communications
underway
Stores conditions
for up to numbers
49 to 64
Stores the local or remote station numbers while they are
communicating the initial data with their relevant master
station.
SD1224
SD1225
SD1226
SD1227
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
L/R
16
L/R
15
L/R
14
L/R
13
L/R
12
L/R
11
L/R
10
L/R
9
L/R
8
L/R
7
L/R
6
L/R
5
L/R
4
L/R
3
L/R
2
L/R
1
L/R
32
L/R
31
L/R
30
L/R
29
L/R
28
L/R
27
L/R
26
L/R
25
L/R
24
L/R
23
L/R
22
L/R
21
L/R
20
L/R
19
L/R
18
L/R
17
L/R
48
L/R
47
L/R
46
L/R
45
L/R
44
L/R
43
L/R
42
L/R
41
L/R
40
L/R
39
L/R
38
L/R
37
L/R
36
L/R
35
L/R
34
L/R
33
L/R
64
L/R
63
L/R
62
L/R
61
L/R
60
L/R
59
L/R
58
L/R
57
L/R
56
L/R
55
L/R
54
L/R
53
L/R
52
L/R
51
L/R
50
L/R
49
Bit
Device
number
The bit corresponding to the station number which is
currently communicating the initial settings becomes "1" .
Example: When stations 23 and 45 are communicating,
bit 6 of SD1225 and bit 12 of SD1226
become "1", and when SD1225 is monitored,
its value is "64 (40
H
)", and when SD1226 is
monitored, its value is "4096 (1000
H
)"
D9228 SD1228
Stores conditions
for up to numbers
1 to 16
D9229 SD1229
Stores conditions
for up to numbers
17 to 32
D9230 SD1230
Stores conditions
for up to numbers
33 to 48
D9231 SD1231
Local station
and remote I/O
station error
Stores conditions
for up to numbers
49 to 64
Stores the local or remote station numbers which are in
error.
SD1228
SD1229
SD1230
SD1231
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
L/R
16
L/R
15
L/R
14
L/R
13
L/R
12
L/R
11
L/R
10
L/R
9
L/R
8
L/R
7
L/R
6
L/R
5
L/R
4
L/R
3
L/R
2
L/R
1
L/R
32
L/R
31
L/R
30
L/R
29
L/R
28
L/R
27
L/R
26
L/R
25
L/R
24
L/R
23
L/R
22
L/R
21
L/R
20
L/R
19
L/R
18
L/R
17
L/R
48
L/R
47
L/R
46
L/R
45
L/R
44
L/R
43
L/R
42
L/R
41
L/R
40
L/R
39
L/R
38
L/R
37
L/R
36
L/R
35
L/R
34
L/R
33
L/R
64
L/R
63
L/R
62
L/R
61
L/R
60
L/R
59
L/R
58
L/R
57
L/R
56
L/R
55
L/R
54
L/R
53
L/R
52
L/R
51
L/R
50
L/R
49
Bit
Device
number
The bit corresponding to the station number with the error
becomes "1" .
Example: When local station 3 and remote I/O station
14 have an error, bits 2 and 13 of SD1228
become "1", and when SD1228 is monitored,
its value is "8196 (2004
H
)".
QnA