Omron CS1W-ETN21 Network Card User Manual


 
95
Automatic Clock Adjustment Error Processing Section 5-4
Note For details on other error log information, refer to the Operation Manual, Con-
struction of Networks: SECTION 8 Troubleshooting.
5-4-3 Error Log Error Codes for the Automatic Clock Adjustment
Function
When an error occurs while the Ethernet Unit is operating, the error code,
detailed error code, and time the error occurred are saved in the error log.
The following table provides a list of the error codes.
The error log can be read by sending FINS commands to the Ethernet Unit or
by using the mail receive function and specifying the ErrorLogRead com-
mand.
Error
code
Meaning Detailed error code Correction EEPROM
1st byte 2nd byte
021A Logic error
in setting
table
00 01: Data link
table
02: Network
parameters
03: Routing
tables
04: Setup
05: CPU Bus
Unit Words
(CIO/DM)
Recreate the data
specified by the
2nd byte of the
detailed error
code.
Saved
03C1 Server set-
ting error
00: DNS
01: SMTP
02: POP3
03: SNTP
01: IP address
02: Host name
03: Port number
04: Other
parameters
Set the server
settings correctly
based on the
information in the
detailed error
code.
---
03C4 Server
connection
error
00: DNS
01: SMTP
02: POP3
03: SNTP
01: Specified
host does not
exist
02: No service
at specified host
03: Timeout
04: Closed uni-
laterally by host
05: Cannot con-
nect because
account infor-
mation does not
match
06: Host name
resolution error
07: Transmis-
sion error
08: Reception
error
09: Other error
Take either of the
following mea-
sures.
• Correct the set-
tings for each
server.
• Inspect the com-
munications
path (Ethernet
Unit, cable con-
nections, hub,
router, server),
and correct the
situation that is
causing the
error.
---