Omron CS1W-ETN21 Network Card User Manual


 
142
Using Socket Services with CMND(490) Section 6-8
Data Flow
The data will flow between the CPU Unit, Ethernet Unit, and host computer as
shown in the following diagram.
Note Here, “execution bits” refer to CIO 000000 to CIO 000003, which are used in
the ladder diagram to control execution of communications and are not sys-
tem flags, such as the Port Enabled Flags (A20200 to A20207).
Basic Operations
CIO 000000 is turned ON to request opening a passive TCP socket from
the Ethernet Unit.
CIO 000001 is turned ON to request closing the TCP socket from the
Ethernet Unit.
CIO 000002 is turned ON to request sending data from the Ethernet Unit.
Data (100 bytes) is sent beginning at D02005.
CIO 000003 is turned ON to request receiving data from the Ethernet
Unit. The data that is received (100 bytes) is stored beginning at D04022.
One of the bits between CIO 000100 and CIO 000103 will turn ON if an
error occurs. Refer to 6-7-5 Socket Service Request Switches for informa-
tion on errors. The following areas can be used to access details about
errors:
CMND(490) response codes
Response codes in results storage area
Network Communications Error Flags (A21900 to A21907)
Completion codes (A203 to A210)
(1) Request Switches
(2) Execution bits turned ON (see Note)
(3) CMND(490) response
(6) Results stored in results
(7) Execution bits turned OFF
CPU UnitEthernet UnitLine
(Ethernet)
Host
computer
(4) Sent to line.
(5) Processing in
host computer