Paradyne 8620 Network Hardware User Manual


 
2. Installation
2-8 July 2003 8620-A2-GN20-40
Complying with NEBS
The following must be taken into consideration for compliance with Network
Equipment-Building System (NEBS) requirements.
Connection to the CO Ground Lug
Procedure
To connect to the CO ground lug:
1. Strip back the insulation approximately 1/4- to 3/8-inch (6.5 to 9.5 mm) on the
14 AWG copper ground wire.
2. Loosen the screw on the GND lug located on the rear surface at the center of
the bottom edge.
3. Insert the stripped end of the wire into the open end of the GND lug and
tighten the lug’s screw. Make sure it makes contact with the stripped portion of
the wire.
ESD Wrist Strap Jack
A noninsulated banana jack is located at the left front of the Hotwire 8620
GranDSLAM to provide a ground for an ESD wrist strap.
HANDLING PRECAUTIONS FOR
STATIC-SENSITIVE DEVICES
This product is designed to protect sensitive components from damage
due to electrostatic discharge (ESD) during normal operation. When
performing installation procedures, however, take proper static control
precautions to prevent damage to equipment. If you are not sure of the
proper static control precautions, contact your nearest sales or service
representative.
!