September 25, 2006 Chapter 3: Provisioning
LTPE-UM-3159-02 3-17
To configure the shelf alarms:
Remote Alarm Reporting
This Config menu option (Figure 3-11) must be enabled when your system is configured for autonomous dial-out
reporting of alarms to a remote management station or printer. If necessary, select the Remote Alarm Reporting
menu item and press ENTER to change the setting from disabled (Dis) to enabled (Ena).
Figure 3-11. Remote Alarm Reporting Menu Item
Set Date and Time
Use the
Æ arrow key to select Config, then press D to display the Set Date/Time dialog box (Figure 3-12 on page
3-18). This dialog box allows you to enter the current Date and Time so the displayed alarm reporting information is
correct.
The Date format is DD/MM/YYYY (day/month/year). The Time format is HH:MM:SS (hour:minute:second) and
displays as a 24-hour clock (01:00:00 through 24:59:59).
Step Action
1
Navigate the menu using the
Ç and È arrow keys on the keyboard.
2 In the Loss of power on one 48V supply field, use the SPACEBAR to select DIS (disabled), MIN
(minimum), MAJ (major), or CRT (critical).
3 In the HDSL alarm if 3 lines down field, use the SPACEBAR to select DIS (disabled), MIN (minimum),
MAJ (major), or CRT (critical).
4 In the Loss of External Clock field (on EMU-830 List 6A only), use the SPACEBAR to select DIS
(disabled), MIN (minimum), MAJ (major), or CRT (critical).
5 In the ACO Retirement of Alarm Relays field, use the SPACEBAR to select DIS (disabled) or ENA
(enabled) for the Audible and Visual fields of the Critical, Major, and Minor alarm relays.
6 Press ENTER to confirm settings and return to the top of the Config menu.
Note: Setting the EMU’s date and time automatically sets the date and time for all HDSL/G.SHDSL cards
in the shelf.