Battery Temperature Probe Installation
The optional temperature probe is used to monitor the battery string temperature. To get the
most representative temperature measurement, the probe should be placed in contact with a
battery cell that is centrally located. The probe should be placed directly in contact with the cell
(not the frame surrounding the cell). Generally, the cell cover can be used; be careful not to
allow the probe body to touch the terminals. Plug the connector end of the temperature probe
into J5 of the control unit backplane card. Route the cable as required positioning the probe on
the selected battery cell. Remove the adhesive protection strip from the probe body and press
the adhesive side of the probe on the battery cell cover.
Figure 3.4-2 Battery Temperature Probe Installation