American Power Conversion MX28B400 Power Supply User Manual


 
MX28B400 +24 VDC User’s Manual Page 10
3.6. DC Power Output Over-Current Protection
DC Circuit Breakers
A standard 24-position plug-in circuit breaker tier provides +24 Vdc distribution. Various circuit
breaker sizes from 1 to 100 amps are available, with 60-100 amp breakers requiring two
positions and a circuit breaker adapter kit. The breaker tier is connected at its center to the +24
Vdc bus, and each side has a current capacity of 300A. It is therefore necessary to balance the
load on the power plant to avoid overloading the output bus. Also when planning the output
installation, take into consideration the configuration of the plant and the number of rectifiers
installed.
Any combination of up to 24 single (1-50 Amp) or up to 12 double (60-100 Amp) breakers may
be installed. Figure 3.6-1 shows the power plant’s distribution section with the front cover
removed.
Figure 3.6-1 DC Distribution (Front Cover Removed)
Plug-in circuit breakers rated at 60A or more require two mounting positions and require a circuit
breaker adapter, which is included in the circuit breaker kit. Adaptors are available with studs
for #10-32 nuts on 5/8” centers, #10-32 nuts on ¾” centers, or ¼-20 nuts on 1” centers. The
circuit breaker kit includes all necessary mounting hardware. Available plug-in circuit breakers
and circuit breaker kits are shown in Figure 3.6-2.