American Power Conversion MX28B400 Power Supply User Manual


 
MX28B400 +24 VDC User’s Manual Page 26
Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Battery Low Temperature
Alarm
Security Level {1}
[BATT/SET-ALM]
The output relay energized if the Battery
Temperature drops below the battery
Low Temperature threshold.
Batt LT Alm m+
Minor
Battery Low Temperature
Threshold Security Level {1}
[BATT/SET-ALM]
Battery Temperature is temperature
measured at the battery probe. An alarm
is generated if the battery temperature
drops below this value.
Batt LT Thr m+
0.0 C
Battery Low Voltage Alarm
Security Level {1}
[BATT/SET-ALM]
The output relay energized if the dc
output voltage drops below the battery
low voltage threshold.
Batt LV Alm m+
Minor
Battery Low Voltage Threshold
Security Level {1}
[BATT/SET-ALM]
An alarm is generated if the dc output
voltage drops below this value.
Batt LV Thr m+
22.00 V
Battery Maximum Recharge
Current
Security Level {1}
[BATT/PARAM]
One of three parameters that control the
dc output voltage. If Battery Current
surpasses the Maximum Battery
Recharge Current, the dc output voltage
will be reduced (the system limits the
charging current to this programmable
value).
Batt Max Rechm+
50 A
Battery Temperature
{Status Only}
[STATUS]
Battery temperature measured by the
system controller at the optional battery
temperature sensor probe.
Batt Temp +
25.2 C
Circuit Breaker 1 Alias
Security Level {1}
[MODULES/CIRBKR/ALIAS]
Circuit Breaker 24 Alias
Security Level {1}
[MODULES/CIRBKR/ALIAS]
An alternate name (alias) that can be
assigned to a circuit breaker if desired.
An alternate name (alias) that can be
assigned to a circuit breaker if desired.
Cir Bkr 1 m+
+24V
Cir Bkr 24 m+
+24V
Circuit Breaker 1 Tripped
Security Level {1}
[MODULES/CIRBKR/SET-
ALM]
Circuit Breaker 24 Tripped
Security Level {1}
[MODULES/CIRBKR/SET-
ALM]
An alarm that indicates Circuit Breaker 1
is tripped.
An alarm that indicates Circuit Breaker
24 is tripped.
Cir Bkr 1 Alm m+
Major
Cir Bkr 24 Almm+
Major
Compensation High Knee
Security Level {1}
[BATT/COMP]
The temperature compensation high
knee is the point above which there is no
additional battery voltage compensation
for further increases in temperature.
Comp Hknee m+
40.0 C