MX28B400 +24 VDC User’s Manual Page 30
Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Output Relay 1 Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
Output Relay 6 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be
assigned to Output Relay 1 if desired.
An alternate name (alias) can be
assigned to Output Relay 6 if desired.
Out-Rly 1 m+
Relay 1
Out-Rly 6 m+
Relay 6
Output Relay 1 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Output Relay 6 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Delay between sensing of the alarm
condition and activation of Output Relay
1. An alarm condition must exist for
longer than the delay to be activated.
Delay between sensing of the alarm
condition and activation of Output Relay
6. An alarm condition must exist for
longer than the delay to be activated.
Out-Rly 1 Dly m+
0 sec
Out-Rly 6 Dly m+
0 sec
Output Relay Major Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be
assigned to the major Relay if desired.
Relay Major
m+
Major
Output Relay Minor Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be
assigned to the Minor Relay if desired.
Relay Minor
m+
Minor
PIN 1 change
Security Level {2}
[SYSTEM/SETUP]
Permanently change password (PIN) that
permits security Level 1 parameter
changes - limited access.
PIN m+
1111
PIN 2 Change
Security Level {2}
[SYSTEM/SETUP]
Permanently change password (PIN) that
permits security Level 2 parameter
changes - unlimited access.
PIN 2 m+
2222
PIN Entry
Security Level {0}
[PIN]
Screen for entry of the active password
(PIN). Before any changes can be
made, the correct pin for the desires
security level must be entered. Level 0 –
full read access. Level 1 –full read and
limited write access. Level 2 – full read
and write access.
PIN m+
0000
Rectifier Communications Fail
Timeout
Security Level {1}
[MODULES/RECT/PARAM]
The maximum rectifier communications
response time allowed before a
communications failure is declared.
RectFailComm m+
1 min
Rectifier Configuration Alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if the rectifier
configuration differs from its stored
configuration. This occurs if a rectifier is
added after configuration.
Rect Cfg Alm m+
Minor