MX28B400 +24 VDC User’s Manual Page 30
Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Output Relay 1 Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
•
•
•
Output Relay 6 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be
assigned to Output Relay 1 if desired.
•
•
•
An alternate name (alias) can be
assigned to Output Relay 6 if desired.
Out-Rly 1 m+
Relay 1
•
•
•
Out-Rly 6 m+
Relay 6
Output Relay 1 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
•
•
•
Output Relay 6 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Delay between sensing of the alarm
condition and activation of Output Relay
1. An alarm condition must exist for
longer than the delay to be activated.
•
•
Delay between sensing of the alarm
condition and activation of Output Relay
6. An alarm condition must exist for
longer than the delay to be activated.
Out-Rly 1 Dly m+
0 sec
•
•
•
Out-Rly 6 Dly m+
0 sec
Output Relay Major Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be
assigned to the major Relay if desired.
Relay Major
m+
Major
Output Relay Minor Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be
assigned to the Minor Relay if desired.
Relay Minor
m+
Minor
PIN 1 change
Security Level {2}
[SYSTEM/SETUP]
Permanently change password (PIN) that
permits security Level 1 parameter
changes - limited access.
PIN m+
1111
PIN 2 Change
Security Level {2}
[SYSTEM/SETUP]
Permanently change password (PIN) that
permits security Level 2 parameter
changes - unlimited access.
PIN 2 m+
2222
PIN Entry
Security Level {0}
[PIN]
Screen for entry of the active password
(PIN). Before any changes can be
made, the correct pin for the desires
security level must be entered. Level 0 –
full read access. Level 1 –full read and
limited write access. Level 2 – full read
and write access.
PIN m+
0000
Rectifier Communications Fail
Timeout
Security Level {1}
[MODULES/RECT/PARAM]
The maximum rectifier communications
response time allowed before a
communications failure is declared.
RectFailComm m+
1 min
Rectifier Configuration Alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if the rectifier
configuration differs from its stored
configuration. This occurs if a rectifier is
added after configuration.
Rect Cfg Alm m+
Minor